BS 6622 Single Core Armoured 22KV XLPE Stranded Copper Conductors
Construction
cross-sectional area mmsq |
Minimum average thickness of insulation mm |
Nominal diameter over insulation
|
Nominal thickness of PVC bedding
mm |
Nominal number and diameter of armoured wires no./mm |
Nominal thickness of PVC oversheath mm |
Nominal overall diameter of cable mm |
50 |
5.5 |
21.6 |
1.2 |
47/1.6 |
2 |
32.7 |
70 |
5.5 |
23.4 |
1.2 |
40/2.0 |
2 |
35.3 |
95 |
5.5 |
25.1 |
1.2 |
43/2.0 |
2.1 |
37.2 |
120 |
5.5 |
26.6 |
1.2 |
45/2.0 |
2.1 |
38.7 |
150 |
5.5 |
27.9 |
1.2 |
47/2.0 |
2.2 |
40.4 |
185 |
5.5 |
29.7 |
1.2 |
49/2.0 |
2.2 |
42.2 |
240 |
5.5 |
31.9 |
1.2 |
52/2.0 |
2.3 |
44.6 |
300 |
5.5 |
34.2 |
1.3 |
45/2.5 |
2.4 |
48.3 |
400 |
5.5 |
36.9 |
1.3 |
48/2.5 |
2.5 |
51.2 |
500 |
5.5 |
39.8 |
1.4 |
52/2.5 |
2.6 |
54.5 |
630 |
5.5 |
43.2 |
1.4 |
55/2.5 |
2.8 |
58.3 |
800 |
Please refer to our technical department for further information |
|||||
1000 |
Installation
cross-sectional area mmsq |
Approximate cable weight kg/m |
Nominal drum length m |
Minimum bending radius mm |
Nominal internal diameter of ducts mm |
50 |
1.6 |
1000 |
600 |
100 |
70 |
1.9 |
500 |
650 |
100 |
95 |
2.3 |
500 |
700 |
100 |
120 |
2.6 |
500 |
700 |
100 |
150 |
2.9 |
500 |
750 |
100 |
185 |
3.4 |
500 |
800 |
100 |
240 |
4.0 |
500 |
850 |
100 |
300 |
4.9 |
500 |
900 |
100 |
400 |
5.8 |
250 |
950 |
100 |
500 |
7.0 |
250 |
1000 |
100 |
630 |
8.4 |
250 |
1050 |
100 |
800 |
Please refer to our technical department for further information |
|||
1000 |
Electrical Performance
cross-sectional area mmsq |
Maximum DC resistance of conductor at 20
¡æ
uohms/m |
Maximum AC resistance of conductor at 90 ¡æ uohms/m |
Reactance at 50Hz uohms/m |
Impedance at 50Hz uohms/m |
Maximum Capacitace PF/m |
Maximum charging current at normal voltage and frequency mA/m |
50 |
387 |
494 |
149 |
515 |
177 |
0.71 |
70 |
268 |
343 |
141 |
370 |
200 |
0.80 |
95 |
193 |
248 |
133 |
281 |
222 |
0.89 |
120 |
153 |
196 |
128 |
234 |
241 |
0.96 |
150 |
124 |
159 |
125 |
201 |
257 |
1.03 |
185 |
99.1 |
128 |
120 |
174 |
280 |
1.12 |
240 |
75.4 |
98 |
116 |
151 |
307 |
1.23 |
300 |
60.1 |
80 |
113 |
137 |
336 |
1.34 |
400 |
47 |
64 |
109 |
125 |
370 |
1.48 |
500 |
36.6 |
51 |
106 |
117 |
406 |
1.62 |
630 |
28.3 |
42 |
102 |
110 |
449 |
1.8 |
800 |
Please refer to our technical department for further information |
|||||
1000 |
Ratings
Cross-sectional area
mmsq |
Current Ratings |
Short circuit ratings |
|||
Laid direct in ground
Amps |
Drawn into ducts
Amps |
Laid in air
Amps |
One second short circuit rating of conductor
KA |
One second short circuit rating of copper per core
KA |
|
50 |
220 |
210 |
260 |
6.8 |
Typically less then 1kA |
70 |
270 |
260 |
320 |
9.8 |
|
95 |
320 |
300 |
380 |
13.3 |
|
120 |
360 |
340 |
440 |
17.2 |
|
150 |
410 |
370 |
490 |
21.2 |
|
185 |
450 |
400 |
560 |
26.6 |
|
240 |
510 |
450 |
650 |
34.9 |
|
300 |
570 |
490 |
730 |
43.8 |
|
400 |
640 |
530 |
830 |
57.3 |
|
500 |
700 |
570 |
940 |
72.3 |
|
630 |
760 |
610 |
1050 |
91.2 |
|
800 |
Please refer to our technical department for further information |
||||
1000 |