KYNAR/HMWPE Cathodic Protection Power Cable

Application

A direct earth burial, DC lead, cathodic protection cable for use in deep anode groundbed installations, designed to withstand corrosive gases.

Standard

  • ASTM specifications D-1248

Construction

Conductor Stranded bare copper conductor conforms to ASTM Specification B-8.
Insulation A homogeneous wall of natural PVDF fluoropolymer (Kynar) shall be extruded over the conductor.
Jacket Insulation is high molecular weight polyethylene conforming to ASTM-D-1248, Type 1, Class A, Category 5, Grades E4 and E5. Tensile Strengths J1, J3 available.

Technical Data

Rated voltage 600V
Max. Operating temperature 150℃

Dimensions

Conductor Size No. of Stranding Circular Mils AWG Diameter HALAR Thickness HMWPE Thickness Nominal Outer Diameter Total weight
    In In In In Lbs/Mft
8 AWG 7 16.51 0.146 0.02 0.065 0.316 83
6 AWG 7 26.24 0.184 0.02 0.065 0.354 120
4 AWG 7 41.74 0.232 0.02 0.065 0.402 177
2 AWG 7 66.36 0.283 0.02 0.065 0.462 260
Contact Us