TW
Application
The TW conductor is suitable for most current wiring solutions for residential, commercial and industrial environments. It is used in branch circuits for permanent installations. TW conductors in sizes 14 AWG to 8 AWG can be installed in conduits and other raceways. The temperature of installation shall not exceed 60oC.
Compliances
- UL 83 - Thermoplastic-Insulated Wires and Cables
- UL 1581 - Electrical Wires, Cables and Flexible Cords
- ASTM B3, B8
Construction
Conductor |
Bare annealed copper conductor, solid or stranded |
Insulation |
PVC 60°C insulation |
Color |
Upon request, black is preferable |
Parameters
AWG or kcmil |
Strand |
Nominal Insulation Thickness |
Nominl Overall Diameter |
Cable Weight |
Inch/mm |
Inch/mm |
Lbs/kft |
kg/km |
14 |
1 |
0.030 |
0.76 |
0.138 |
3.5 |
19 |
28 |
12 |
1 |
0.030 |
0.76 |
0.154 |
3.9 |
27 |
40 |
10 |
1 |
0.030 |
0.76 |
0.177 |
4.5 |
40 |
60 |
8 |
1 |
0.045 |
1.14 |
0.240 |
6.1 |
67 |
100 |
14 |
7 |
0.030 |
0.76 |
0.146 |
3.7 |
19 |
29 |
12 |
7 |
0.030 |
0.76 |
0.165 |
4.2 |
29 |
43 |
10 |
7 |
0.030 |
0.76 |
0.193 |
4.9 |
44 |
65 |
8 |
7 |
0.045 |
1.14 |
0.260 |
6.6 |
72 |
107 |