1KV Heat Shrinkable Indoor and Outdoor Cable Termination Kits

HLVT

     
HLVT Type UA HLVT Type CN HLVT Type A

Application

Indoor and outdoor terminations Type HLVT are designed to cover 3, 3.5 and 4-core plastic insulated cables (with PVC PE XLPE EPR outer sheath) with or without SWA/AWA/STA. The designs cover a wide range of cable cross section.

Features

Excellent electrical insulation

Environment sealing and weathering resistance

High mechanical protection

Wide cross section range suitable for all types of connectors

Compact design

Unlimited shelf life, allowing immediate reenergizing

Standard

EN 50393, DIN VDE 0278-393, BS 7933-2, IEC 60502-4

Kit contents

Adhesive lined core insulation tube
Low voltage breakout
Lug sealing tubes
Corrosion protection sleeve
Support ring and roll spring or armour clamp
Earth braid

Ordering Information

Heat Shrinkable Termination Kits for polymeric insulated cables with mechanical lugs.

Voltage Part no. Cross section mm2 Cable Type (Unarmoured) Connector Type
Uo/U(Um) 0.6/1.0(1.2)kV HLVT-4/1.5-4/I-UA-M or HLVT-4/1.5-4/O-UA-M 1.5-4 UA M
HLVT-4/6-16/I-UA-M or HLVT-46-16/O-UA-M 6-16 UA M
HLVT-4/25-50/I-UA-M or HLVT-4//25-50/O-UA-M 25-50 UA M
HLVT-4/70-120/I-UA-M or HLVT-4/70-120/O-UA-M 70-120 UA M
HLVT-4/150-240/I-UA-M or HLVT-4/150-240/O-UA-M 150-240 UA M

Heat Shrinkable Termination Kits for polymeric insulated cables with crimp lugs.

Voltage Part no. Cross section mm2 Cable Type (Unarmoured) Connector Type
Uo/U(Um) 0.6/1.0(1.2)kV HLVT-4/1.5-4/I-UA-C or HLVT-4/1.5-4/O-UA-C 1.5-4 UA C
HLVT-4/6-16/I-UA-C or HLVT-4/6-16/O-UA-C 6-16 UA C
HLVT-4/25-50/I-UA-C or HLVT-4/25-50/O-UA-C 25-50 UA C
HLVT-4/70-120/I-UA-C or HLVT-4/70-120/O-UA-C 70-120 UA C
HLVT-4/150-240/I-UA-C or HLVT-4/150-240/O-UA-C 150-240 UA C

Heat Shrinkable Termination Kits for polymeric insulated cables (concentric neutral) with mechanical lugs.

Voltage Part no. Cross section mm2 Cable Type (concentric neutra) Connector Type
Uo/U(Um) 0.6/1.0(1.2)kV HLVT-4/10-25/I-CN-M or HLVT-4/10-25/O-CN-M 10 -25 CN M
HLVT-4/35-50/I-CN-M or HLVT-4/35-50/O-CN-M 35 -50 CN M
HLVT-4/70-120/I-CN-M or HLVT-4/70-120/O-CN-M 70 -120 CN M
HLVT-4/150-240/I-CN-M or HLVT-4/150-240/O-CN-M 150 -240 CN M

Heat Shrinkable Termination Kits for polymeric insulated cables (concentric neutral) with crimp lugs.

Voltage Part no. Cross section mm2 Cable Type (concentric neutra) Connector Type
Uo/U(Um) 0.6/1.0(1.2)kV HLVT-4/10-16/I-CN-C or HLVT-4/10-16/O-CN-C 10 -16 CN C
HLVT-4/25-50/I-CN-C or HLVT-4/25-50/O-CN-C 25 -50 CN C
HLVT-4/70-150/I-CN-C or HLVT-4/70-150/O-CN-C 70 -150 CN C
HLVT-4/185-300/I-CN-C or HLVT-4/185-300/O-CN-C 185 -300 CN C

Heat Shrinkable Termination Kits for armoured polymeric insulated cables with mechanical/bolted lugs.

Voltage Part no. Cross section mm2 Cable Type (armoured) Connector Type
  HLVT-4/1.5-10/I-A-M or HLVT-4/1.5-10/O-A-M 1.5-10 A M
HLVT-4/10-25/I-A-M or HLVT-4/10-25/O-A-M 10 -25 A M
HLVT-4/35-50/I-A-M or HLVT-4/35-50/O-A-M 35 -50 A M
HLVT-4/70-120/I-A-M or HLVT-4/70-120/O-A-M 70 -120 A M
HLVT-4/150-240/I-A-M or HLVT-4/150-240/O-A-M 150 -240 A M

Heat Shrinkable Termination Kits for armoured polymeric insulated cables with crimp lugs.

Voltage Part no. Cross section mm2 Cable Type (armoured) Connector Type
Uo/U(Um) 0.6/1.0(1.2)kV HLVT-4/1.5-4/I-A-C or HLVT-4/1.5-4/O-A-C 1.5-4 A C
HLVT-4/6-16/I-A-C or HLVT-4/6-16/O-A-C 6-16 A C
HLVT-4/25-50/I-A-C or HLVT-4/25-50/O-A-C 25-50 A C
HLVT-4/70-150/I-A-C or HLVT-4/70-150/O-A-C 70-150 A C
HLVT-4/185-300/I-A-C or HLVT-4/185-300/O-A-C 185-300 A C

Example: Kit part number : HLVT- 4/A/O-A -C

Where: HLVT- Heat Shrinkable Low Voltage Cable Terminations; 4-number of cable cores; A-cross section range of cable conductor; O-outdoor termination; A-the type of cable armour,SWA/AWA/STA; C- crimp type lugs.

No lugs supplied unless specified.

Technical Parameters

Performance of heat shrinkable low voltage cable terminations when tested according to EN 50393 (CENELEC 623 S1).

Test sequence Item Requirements acc. to Iec 60502.4 Results Performed test acc. to en 50393
1 Impulse Withstand Voltage Test No breakdown shall occur at 10 positive and 10 negative impulses of 20kV No breakdown shall occur at 10 positive and 10 negative impulses of 20kV Pass
2 AC Withstand Voltage Test (In Air and Ambient Temperature) 4kV,1min No breakdown 4kV,1min No breakdown Pass
3 Insulation Resistance (in Air and Ambient Temperature) ≥ 50MΩ ≥ 50MΩ Pass
4 Impact Test (In Air and Ambient Temperature) 4kg wedge dropped from a height of 1000mm No functional Damage Pass
5 AC Withstand Voltage Test Immersed in the water of with a Height of 1000mm 4kV,1min No breakdown 4kV,1min No breakdown Pass
6 Heating Cycle Test in Air Heat the conductor to 95℃- 100℃,63 times in air, No breakdown Heat the conductor to 95℃- 100℃, 63 times in air, No breakdown Pass
7 Heating Cycle Test (Immersed in the Water of with a Height of 1000mm) Heat the conductor to 95℃- -100℃,63 times in the water, No breakdown Heat the conductor to 95℃- -100℃,63 times in the water, No breakdown Pass
8 AC Withstand Voltage Test (Immersed in the Water of with a Height of 1000mm) 4kV,1min No breakdown 4kV,1min No breakdown Pass
9 Insulation Resistance (in Air and Ambient Temperature) ≥ 50MΩ ≥ 50MΩ Pass