Type G Three-Conductor Round Portable Power Cable 2kV

Applications

These cables are designed for use with mobile mining equipment, such as continuous miners, cutting or loading machines, conveyors, drills or pumps.

Standards

  • ICEA S-75-381/NEMA WC 58
  • ASTM B 172
  • ASTM B 33
  • CAN/CSA C22.2 No. 96

Construction

Type G Three-Conductor Round Portable Power Cable 2kV
Conductors Stranded annealed tinned copper conductor.
Insulation Ethylene Propylene Rubber (EPR).
Grounding Conductor Tinned copper conductor with an optional green outer covering.
Jacket Reinforced heavy-duty/extra-heavy-duty Chlorinated Polyethylene (CPE), black. (Cables having a nominal outside diameter of more than 2.0 inches require extra-heavy-duty jackets.)

Options

Other jacket materials such as CSP/PCP/NBR/PVC are available upon request.

Two-layer jacket with reinforcing fibre between the two layers can be offered as an option.

Mechanical and Thermal Properties

Minimum Bending Radius 6×OD
Maximum Conductor Operating Temperature +90℃

Dimensions and Weight

Construction No. of Strands Grounding Conductor Size Nominal Insulation Thickness Nominal Jacket Thickness Nominal Overall Diameter Height×Width Nominal Weight Ampacity
No. of cores × AWG/kcmil - AWG/kcmil inch mm inch mm inch mm lbs/kft kg/km A
3×8 133 10 0.06 1.5 0.125 3.2 0.91 23.1 590 878 59
3×6 168 10 0.06 1.5 0.140 3.6 1.01 25.7 760 1131 79
3×4 259 8 0.06 1.5 0.155 3.9 1.17 29.7 1070 1592 104
3×3 329 8 0.06 1.5 0.155 3.9 1.24 31.5 1280 1904 120
3×2 259 8 0.06 1.5 0.155 3.9 1.34 34.0 1530 2276 138
3×1 329 7 0.08 2.0 0.170 4.3 1.51 38.4 1890 2812 161
3×1/0 259 6 0.08 2.0 0.170 4.3 1.65 41.9 2320 3452 186
3×2/0 329 5 0.08 2.0 0.190 4.8 1.75 44.5 2700 4017 215
3×3/0 413 4 0.08 2.0 0.190 4.8 1.89 48.0 3270 4865 249
3×4/0 532 3 0.08 2.0 0.205 5.2 2.04 51.8 3970 5907 287
3×250 608 2 0.095 2.4 0.220 5.6 2.39 60.7 5080 7558 320
3×300 741 1 0.095 2.4 0.235 6.0 2.56 65.0 6080 9046 357
3×350 855 1 0.095 2.4 0.235 6.0 2.68 68.1 7140 10623 394
3×400 988 1/0 0.095 2.4 0.250 6.4 2.82 71.6 7780 11575 430
3×500 1221 2/0 0.095 2.4 0.250 6.4 3.03 77.0 9065 13487 487

Ampacity-Based on a conductor temperature of 90℃ and an ambient air temperature of 40℃, per ICEA S-75-381.