SY PVC /PVC/GSWB/PVC Control Cable
Application: For use as a measuring, control and signal cable for the machine tool industry, plant construction, heating and air conditioning, and as a flexible cable between fixed and mobile equipment. The cable is well protected against mechanical damage by the narrow weave steel-wire braid.
• Note: should not be used in any installations where the cable is subjected to repetitive flexing.
Standards: Generally BS6500 VDE0250
Conductor: Class 5 annealed copper conductors to BS6360 / VDE0295
Insulation: PVC
Bedding: PVC
Braiding: Galvanized Steel Wire Braid (GSWB)
Sheath: PVC (Type TM2 to BS7655)
Voltage Rating: 300/500V
Tempe rature rating:Flexing -15 to +70°C,Static -35 to +70°C
Minimum bending radius: 6 x overall diameter
Core identification: Black with White numbers. (3 core and above to include Green/Yellow)
Coloured cores available on request
Current Carrying Capacity (amperes)
Nominal Cross Sectional Area |
Single Phase AC or DC |
Three Phase AC |
mm2 |
Amps |
Amps |
0.5 |
3 |
3 |
0.8 |
6 |
6 |
1.0 |
10 |
10 |
1.5 |
16 |
16 |
2.5 |
25 |
20 |
4.0 |
32 |
25 |
6.0 |
51 |
43 |
10.0 |
70 |
60 |
16.0 |
94 |
80 |
16.0 |
94 |
80 |
The above ratings are based on cable in Free air, in an ambient air temperature of 30°C.
For ambient air temperatures other than 30°C the following rating factors should be applied:
Ratings for cables up to and including 4mm2 are based on 60°C conductor operating temperature with 6mm2 and above based on 70°C operating temperature.
Correction Factors
Cables Up To and Including 4mm2 . Assuming 60°C Conductor Temperature
Ambient Temperature |
35°C |
40°C |
45°C |
50°C |
55°C |
Correction Factor |
0.91 |
0.82 |
0.71 |
0.58 |
0.41 |
Ambient Temperature |
35°C |
40°C |
45°C |
50°C |
55°C |
60°C |
Correction Factor |
0.91 |
0.82 |
0.71 |
0.58 |
0.41 |
0.50 |
3 Core SY control cable
4 Core SY control cable
5 Core SY control cable
7 Core SY control cable