SY PVC /PVC/GSWB/PVC Control Cable

Application: For use as a measuring, control and signal cable for the machine tool industry, plant construction, heating and air conditioning, and as a flexible cable between fixed and mobile equipment. The cable is well protected against mechanical damage by the narrow weave steel-wire braid.
•  Note: should not be used in any installations where the cable is subjected to repetitive flexing.
Standards: Generally BS6500 VDE0250
Conductor: Class 5 annealed copper conductors to BS6360 / VDE0295
Insulation: PVC
Bedding: PVC
Braiding: Galvanized Steel Wire Braid (GSWB)
Sheath: PVC (Type TM2 to BS7655)
Voltage Rating: 300/500V
Tempe rature rating:Flexing -15 to +70°C,Static -35 to +70°C
Minimum bending radius: 6 x overall diameter
Core identification: Black with White numbers. (3 core and above to include Green/Yellow)
Coloured cores available on request
Current Carrying Capacity (amperes)

Nominal Cross Sectional Area

Single Phase AC or DC

Three Phase AC

mm2

Amps

Amps

0.5

3

3

0.8

6

6

1.0

10

10

1.5

16

16

2.5

25

20

4.0

32

25

6.0

51

43

10.0

70

60

16.0

94

80

16.0

94

80

The above ratings are based on cable in Free air, in an ambient air temperature of 30°C.

For ambient air temperatures other than 30°C the following rating factors should be applied:
Ratings for cables up to and including 4mm2 are based on 60°C conductor operating temperature with 6mm2 and above based on 70°C operating temperature.

Correction Factors
Cables Up To and Including 4mm2 . Assuming 60°C Conductor Temperature

Ambient Temperature

35°C

40°C

45°C

50°C

55°C

Correction Factor

0.91

0.82

0.71

0.58

0.41


Cables 6mm2 and above . Assuming 70°C Conductor Temperature

Ambient Temperature

35°C

40°C

45°C

50°C

55°C

60°C

Correction Factor

0.91

0.82

0.71

0.58

0.41

0.50

3 Core SY control cable
4 Core SY control cable
5 Core SY control cable
7 Core SY control cable