Product Name/Code: 7-2-2C SCREENED | Electrical Performance |
||
Application: | Max.Conductor DC Resistance at 20 ℃(Ω/Km) 22.49 |
<84.80 |
|
Multi-conductor-audio,control.& Instrumentation Cables. | Operating Temperature( ℃ ) 74 |
80 |
|
Construction |
Voltage Rating(V) 1499 |
30 |
|
2 Core | Stranded Tinned Copper | 20 ℃ Insulation Resistance(M Ω .KM) |
> 200 |
AWG | 24 |
||
Construction | T0.20 x 7 | ||
Conductor Diameter (mm) | 0.60 | ||
Insulation | PVC | ||
Thickness | 0.3 | ||
Insulation Diameter(mm) | 1.20 | ||
Insulation Color | According customer | ||
Mylar Spiral twist(over lapping,%) | >=25% | ||
Screening | Tinned Copper | ||
Construction(mm) | T0.12 x 16 x4 | ||
Coverage Area(%) | > 70% | ||
Nylon rip cord | 210D | ||
Sheathing | PVC OR LSF | ||
Thickness(mm) | 0.8 | ||
Diameter(mm) | 4.10 | ||
Sheathing Compound | PVC/LSF/LSOH | ||
Core Identification/Color Code | According to customer request | ||
Bending Radius | 6xOverall Diameter | ||
Temperature Rating | 70C | ||
Voltage Rating | 300/500V | ||
Fire Performance | |||
Flame Propagation Test to IEC 60332 Part 1 and Part 3 Determination of the amount Halogen Acid Gas to IEC 60754 Part 1 Smoke Density Test to IEC 61034 Oxygen Index Test to BS 2863 or ISO 4589-2 Temperatre Index Test to BS 2782 or ISO 4589-3 Fire Resistant Test to IEC 60331-24 |
|||
Website: www.caledonian-cables.co.uk | |||
E-mail: sales@caledonian-cables.co.uk | |||