600/1000V Two Core, XLPE Insulated, PVC Sheathed, Unarmoured & Armoured to IEC 60502
Construction
Conductor : Plain annealed copper
Insulation : XLPE Compound
Filler: PVC or Polypropylene yarn
Binder Tape: Polyester (mylar) tape
Bedding: Flame retardant PVC compound
Armouring: Steel wire armored
Sheath: Flame retardant PVC compound
Colour of identification : Red & Black
Sheath Colour : Black, Grey or White
Size of Conductor |
Nominal Thickness of Insulation |
UNARMOURED CABLE |
STEEL WIRE ARMOURED (SWA) CABLE |
Nominal Thickness of Sheath |
Approx. Overall Diameter |
Approx. Weight |
NominalThickness of Bedding |
Nominal Dia. of Armour Wire |
Nom. Thickness of Sheath |
Approx. Overall Diametr |
Approx. Weight |
mm2 |
mm |
mm |
mm |
kg/km |
mm |
mm |
mm |
mm |
kg/km |
1.5 |
0.7 |
1.8 |
10.0 |
125 |
1.0 |
0.9 |
1.8 |
13.5 |
340 |
2.5 |
0.7 |
1.8 |
10.5 |
160 |
1.0 |
0.9 |
1.8 |
14.5 |
390 |
4 |
0.7 |
1.8 |
12.0 |
205 |
1.0 |
0.9 |
1.8 |
15.5 |
460 |
6 |
0.7 |
1.8 |
13.0 |
260 |
1.0 |
0.9 |
1.8 |
17.0 |
535 |
10 |
0.7 |
1.8 |
15.0 |
375 |
1.0 |
1.25 |
1.8 |
19.0 |
800 |
16 |
0.7 |
1.8 |
17.0 |
530 |
1.0 |
1.25 |
1.8 |
21.5 |
1020 |
25 |
0.9 |
1.8 |
17.0 |
655 |
1.0 |
1.6 |
1.8 |
22.0 |
1265 |
35 |
0.9 |
1.8 |
18.5 |
865 |
1.0 |
1.6 |
1.8 |
23.5 |
1535 |
50 |
1.0 |
1.8 |
21.0 |
1135 |
1.0 |
1.6 |
1.8 |
25.5 |
1865 |
70 |
1.1 |
1.8 |
23.5 |
1570 |
1.0 |
1.6 |
2.0 |
29.0 |
2445 |
95 |
1.1 |
1.9 |
26.5 |
2120 |
1.2 |
2.0 |
2.1 |
33.0 |
3345 |
120 |
1.2 |
2.0 |
29.5 |
2640 |
1.2 |
2.0 |
2.2 |
36.0 |
3990 |
150 |
1.4 |
2.2 |
33.0 |
3250 |
1.2 |
2.0 |
2.3 |
39.0 |
4730 |
185 |
1.6 |
2.3 |
36.5 |
4050 |
1.4 |
2.5 |
2.5 |
44.5 |
6160 |
240 |
1.7 |
2.5 |
46.0 |
5300 |
1.4 |
2.5 |
2.7 |
53.5 |
7820 |
300 |
1.8 |
2.6 |
50.0 |
6590 |
1.6 |
2.5 |
2.8 |
58.0 |
9390 |
400 |
2.0 |
2.9 |
54.0 |
8365 |
1.6 |
2.5 |
3.1 |
62.0 |
11475 |
|