600/1000V ABC –Aerial Bundled Cables to HD 626 S1 (AL/XLPE)

Application

The aerial bundled cables designed for fixed installation as overhead power lines up to 1000 V incl.

Standard

HD 626 S1

Construction

Conductor Aluminium conductor, round stranded compressed (RM)
Insulation XLPE

Technical Data

Rated voltage kV 0.6/1
Test voltage Veff kV/Hz 4/50
Laying temperature °C min. -20
Operating temperature °C -30 bis +80
Conductor temperature °C max. +80
Short-circuit temperature °C/s max. +130 /5
Bending radius (min.) mm 18 × O of cable

Dimensions

Number of cores x nominal cross section min. breaking load of conductor strand Current rating in the air Outer diameter Total weight
mm^2 kN A mm kg/km
2x 16 RM 1,910 2,5 72 147
2x 25 RM 1,200 4,0 107 208
2x 35 RM 0,868 5,5 132 277
2x 50 RM 0,641 8,0 165 361
4x 16 RM 1,910 2,5 72 286
4x 25 RM 1,200 4,0 107 430
4x 35 RM 0,868 5,5 132 553
4x 50 RM 0,641 8,0 165 746
4x 70 RM 0,443 10,7 205 1009
4x 95 RM 0,320 13,7 240 1332
4x 120 RM 0,253 18,6 290 1632
4x 35 + 1x 35 RM 0,868/0,868 5,5/5,5 132/132 694
4x 50 + 1x 25 RM 0,641/1,200 8,0/4,0 165/107 814
4x 50 + 1x 35 RM 0,641/0,868 8,5/5,5 165/132 845
4x 70 + 1x 25 RM 0,443/1,200 10,7/4,0 205/107 1105
4x 70 + 2x 25 RM 0,443/1,200 10,7/4,0 205/107 1217
4x 70 + 1x 35 RM 0,443/0,868 10,7/5,5 205/132 1150
4x 70 + 2x 35 RM 0,443/0,868 10,7/5,5 205/132 1289
4x 95 + 1x 25 RM 0,320/1,200 13,7/4,0 240/107 1438
4x 95 + 1x 35 RM 0,320/0,868 13,7/5,5 240/132 1467
4x 95 + 2x 25 RM 0,320/1,200 13,7/4,0 240/107 1544

other cross-sections on request

Contact Us

Add the link of current page.

Clear

Submit

Instant Messaging

WhatsApp :

+852 6230 0392

Skype :

Caledonian Cables

live:1cb87739a29fb08c

Wechat :
The personal information you enter is only used to reply to your message, It will not be leaked or used for other purposes.