600/1000V ABC –Aerial Bundled Cables to IEC 60502 & TNB Specification (AL/PE)

Application

The aerial bundled cables designed for overhead distribution lines have an insulated neutral messenger made of AAAC, which the insulation aluminium phase conductors are helically wound over it. Can be used for fixed installation as overhead power lines up to 1000 V incl.

Standard

  • TNB Specification
  • IEC 60502

Construction

Phase Conductor H68 condition aluminium conductor, round stranded compressed.
Neutral or Messenger Conductor Alloy aluminium conductor, round stranded compressed.
Street Lighting Conductor H68 condition aluminium conductor, round stranded compressed.
Insulation PE.
Assembly The cable consists of insulated phase and street lighting aluminium conductors, shall be held firmly onto the insulated neutral messenger aluminium alloy conductor in a right hand (Z) lay.

Dimensions

Number of cores x nominal cross section min. breaking load of conductor strand Current rating in the air Outer diameter Total weight
mm^2 kN A mm kg/km
1x16+1x 25 RM 6.4 61 15.3 160
3x16+1x 25 RM 6.4 61 19.0 290
3x25+1x 25 RM 6.4 84 23.2 400
3x35+1x 25 RM 6.4 104 25.6 500
3x50+1x 35 RM 8.9 129 30.0 680
3x70+1x 50 RM 12.1 167 34.9 920
3x95+1x 70 RM 18.0 209 40.6 1270
3x120+1x 70 RM 18.0 246 44.1 1510
3x150+1x 95 RM 24.2 283 49.2 1870
3x185+1x120 RM 30.8 332 54.9 2340
3x25+1x25+1x16 RM 6.4 84 23.2 470
3x35+1x25+1x16 RM 6.4 104 25.6 560
3x50+1x35+1x16 RM 8.9 129 30.0 740
3x70+1x50+1x16 RM 12.1 167 34.9 980
3x95+1x70+1x16 RM 18.0 209 40.6 1330
3x120+1x70+1x16 RM 18.0 246 44.1 1580
3x150+1x95+1x16 RM 24.2 283 49.2 1940
3x185+1x120+1x16 RM 30.8 332 54.9 2410

other cross-sections on request