Push Button Cable FFX200 05mRZ1-R/F 2G0.5
APPLICATIONS
The cables are multicore stranded flexible cables sheathed with thermoplastic LSZH compound. The cables have the ability to restrict the propagation of the flame in the event of a fire. This is especially important to slow down the spreading of the fire as the cables may pass from one area to another within a building. Applications can be found in control and power circuits, power stations, underground tunnels, lifts, escalators, and high-rise buildings.
STANDARDS
Basic design | BS 7629-1 |
Halogen Free | IEC 60754-1 |
No corrosive gas emission | IEC 60754-2 |
Minimum Smoke Emission | IEC 61034-1/2 |
Reduced Fire Propagation | IEC 60332-3C / NF C 32070-2.2 (C1) |
Flame Retardance | IEC 60332-1 / NF C 32-070-2.1 (C2) |
Fire Resistance | IEC 60331 / NF C 32070-2.3(CR1) |
VOLTAGE RATING
300/500V
CONSTRUCTION
Conductor : Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2 or class 5.
Insulation : Mica glass tape covered by extruded cross-linked XLPE compound.
Outer Sheath : Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1.
ELECTRICAL PROPERTIES
Dielectric test: | 2000 V r.m.s. x 5’ (core/core) |
Insulation resistance | 1000 MΩ x km (at 20°C) |
Short circuit temperature | 250°C |
PHYSICAL AND THERMAL PROPERTIES
Temperature range during operation (fixed state) : -30°C – +90°C
Temperature range during installation (mobile state) : -20°C – +50°C
Minimum bending radius : 8 × Overall Diameter
CONSTRUCTION PARAMETERS
FFX200 05mRZ1-R 2G0.5
FFX200 05mRZ1-F 2G0.5
No.of core | Nominal Cross Sectional Area | Number & Nominal Diameter of Strands | Nominal Insulation Thickness | Nominal Sheath Thickness | Nominal Overall Diameter | Approx. Weight |
---|---|---|---|---|---|---|
mm² | No/mm | mm | mm | mm | kg/km | |
2 | 0.5 | 7/0.31 | 0.5 | 0.5 | 6.5 | 45 |
2 | 0.5 | 16/0.2 | 0.5 | 0.5 | 6.5 | 45 |