BS 6724 Armoured Power Cables, 1900/3300V
Applications
These cables are used for power and control circuits, they can offer excellent protection through the use of a heavy galvanized steel wire armour. The GSWA makes them suitable for use inside and outside buildings or for direct burial in the ground. For installation where fire, smoke emission and toxic fumes create a potential threat to life and equipment.
Construction
Conductor |
Solid Aluminum or Annealed Copper conductor, circular or shaped, Class 2 to BS EN60228. |
Insulation |
XLPE (Cross-Linked Polyethylene) Type GP 8 conforming to BS 7655-1.3 or type GP 6 conforming to BS 7655-1.2. |
Colour Code |
1 Core : Brown or Blue |
2 Cores : Brown, Blue |
3 Cores : Brown, Black, Grey |
4 Cores : Blue, Brown, Black, Grey |
5 Cores : Green/Yellow, Blue, Brown, Black, Grey |
Above 5 Cores : White Cores with black numbers |
Bedding |
The bedding shall consist of an extruded layer of polymeric material consistent with the operating temperature of the cable. |
Armour |
Single Core : AWA (Aluminum Wire Armour) |
Multi Core : GSWA (Galvanized Steel Wire Armour) |
Outer Sheath |
LSOH (Low Smoke Zero Halogen),conforming to BS 7655-6.1. |
Technical Information
Voltage rating |
1900/3300V |
Temperature rating |
0°C to +90°C |
Bending radius |
1.5mm² to 16mm² : 6 x overall diameter |
25mm² and above : 8 x overall diameter |
Flame retardant |
BS EN 60332-1-2 ; BS EN 60332-3-24:2009 |
Halogen free |
BS EN 60754-1 |
Smoke density |
BS EN 61034-2 |
Cable Parameter
Single-core 1900/3300 V cables with circular stranded copper conductor |
|
Nominal Cross-sectional Area |
Strand Type |
Nominal Insulation Thickness |
Nominal Bedding Thickness |
Nominal Alum Wire Armor dia. |
Nominal Sheath Thickness |
Approx. Overall Diameter |
Aprrox Weight |
mm² |
No./mm |
mm |
mm |
mm |
mm |
mm |
kg/km |
1x50 |
19/1.78 |
2 |
0.8 |
1.25 |
1.6 |
20.6 |
790 |
1x70 |
19/2.14 |
2 |
0.8 |
1.25 |
1.6 |
22.4 |
1040 |
1x95 |
19/2.52 |
2 |
0.8 |
1.25 |
1.6 |
24.3 |
1330 |
1x120 |
37/2.03 |
2 |
1 |
1.6 |
1.7 |
27.2 |
1680 |
1x150 |
37/2.25 |
2 |
1 |
1.6 |
1.7 |
28.8 |
1970 |
1x185 |
37/2.52 |
2 |
1 |
1.6 |
1.8 |
30.8 |
2370 |
1x240 |
61/2.25 |
2 |
1 |
1.6 |
1.8 |
33.5 |
2960 |
1x300 |
61/2.52 |
2 |
1 |
1.6 |
1.9 |
36.1 |
3610 |
1x400 |
61/2.85 |
2 |
1.2 |
2 |
2 |
40.5 |
4600 |
1x500 |
61/3.20 |
2.2 |
1.2 |
2 |
2.1 |
44.2 |
5680 |
1x630 |
127/2.52 |
2.4 |
1.2 |
2 |
2.2 |
48.8 |
7160 |
1x800 |
127/2.85 |
2.6 |
1.4 |
2.5 |
2.4 |
55.4 |
9150 |
1x1000 |
127/3.20 |
2.8 |
1.4 |
2.5 |
2.5 |
60.6 |
11270 |
Single-core 1900/3300 V cables with solid aluminum conductor |
|
Nominal Cross-sectional Area |
Nominal Insulation Thickness |
Nominal Bedding Thickness |
Nominal Alum Wire Armor dia. |
Nominal Sheath Thickness |
Approx. Overall Diameter |
Aprrox Weight |
mm² |
mm |
mm |
mm |
mm |
mm |
kg/km |
1x50 |
2 |
0.8 |
1.25 |
1.6 |
19.4 |
600 |
1x70 |
2 |
0.8 |
1.25 |
1.6 |
20.9 |
710 |
1x95 |
2 |
0.8 |
1.25 |
1.6 |
22.5 |
810 |
1x120 |
2 |
1 |
1.6 |
1.7 |
25.2 |
1065 |
1x150 |
2 |
1 |
1.6 |
1.7 |
26.5 |
1210 |
1x185 |
2 |
1 |
1.6 |
1.8 |
28.3 |
1390 |
1x240 |
2 |
1 |
1.6 |
1.8 |
30.5 |
1630 |
1x300 |
2 |
1 |
1.6 |
1.9 |
32.8 |
1900 |
Three-core 1900/3300 V cables with stranded copper conductors |
|
Nominal Cross-sectional Area |
Strand Type |
Nominal Insulation Thickness |
Nominal Bedding Thickness |
Nominal Steel Wire Armor dia. |
Nominal Sheath Thickness |
Approx. Overall Diameter |
Aprrox Weight |
mm² |
No./mm |
mm |
mm |
mm |
mm |
mm |
kg/km |
3x16 |
7/1.70 |
2 |
1 |
1.6 |
1.8 |
29.3 |
1600 |
3x25 |
7/2.14 |
2 |
1 |
1.6 |
1.8 |
32.2 |
2060 |
3x35 |
7/2.52 |
2 |
1 |
1.6 |
1.9 |
34.8 |
2400 |
3x35* |
7/2.52 |
2 |
1 |
1.6 |
1.9 |
31.1 |
2400 |
3x50* |
19/1.78 |
2 |
1.2 |
2 |
2 |
34.7 |
3200 |
3x70* |
19/2.14 |
2 |
1.2 |
2 |
2.1 |
38 |
3800 |
3x95* |
19/2.52 |
2 |
1.2 |
2 |
2.2 |
41.4 |
4730 |
3x120* |
37/2.03 |
2 |
1.4 |
2.5 |
2.3 |
45.7 |
6070 |
3x150* |
37/2.25 |
2 |
1.4 |
2.5 |
2.4 |
48.5 |
7010 |
3x185* |
37/2.52 |
2 |
1.4 |
2.5 |
2.5 |
51.9 |
8270 |
3x240* |
61/2.25 |
2 |
1.6 |
2.5 |
2.6 |
56.9 |
10310 |
3x300* |
61/2.52 |
2 |
1.6 |
2.5 |
2.7 |
61.2 |
12300 |
3x400* |
61/2.85 |
2 |
1.6 |
2.5 |
2.9 |
66.6 |
14500 |
* Shaped stranded conductor (class 2)
Three-core 1900/3300 V cables with solid aluminum conductors |
|
Nominal Cross-sectional Area |
Nominal Insulation Thickness |
Nominal Bedding Thickness |
Nominal Steel Wire Armor dia. |
Nominal Sheath Thickness |
Approx. Overall Diameter |
Aprrox Weight |
mm² |
mm |
mm |
mm |
mm |
mm |
kg/km |
3x16 |
2 |
1 |
1.6 |
1.8 |
27.9 |
1540 |
3x25 |
2 |
1 |
1.6 |
1.8 |
30.4 |
1780 |
3x35 |
2 |
1 |
1.6 |
1.9 |
32.7 |
2040 |
3x35* |
2 |
1 |
1.6 |
1.9 |
29.7 |
2040 |
3x50* |
2 |
1.2 |
2 |
2 |
33 |
2760 |
3x70* |
2 |
1.2 |
2 |
2.1 |
36 |
3210 |
3x95* |
2 |
1.2 |
2 |
2.2 |
39.1 |
3625 |
3x120* |
2 |
1.4 |
2.5 |
2.3 |
43.1 |
4820 |
3x150* |
2 |
1.4 |
2.5 |
2.4 |
45.6 |
5410 |
3x185* |
2 |
1.4 |
2.5 |
2.5 |
48.7 |
6070 |
3x240* |
2 |
1.6 |
2.5 |
2.6 |
53.2 |
7150 |
3x300* |
2 |
1.6 |
2.5 |
2.7 |
57.2 |
8120 |
* Solid shaped conductor (class 1)