Technical Reference
Maximum resistance of conductor and armour for single-core cable having aluminum wire armour
Nominal cross sectional area of conductor |
Maximum resistance per km of cable at 20 °C |
Copper conductor |
Aluminum conductor |
Aluminum wire armour |
Cables with stranded copper conductor |
Cables with solid aluminum conductor |
600/1000 V |
1900/3300 V |
600/1000 V |
1900/3300 V |
mm2 |
Ω |
Ω |
Ω |
Ω |
Ω |
Ω |
50 |
0.387 |
0.641 |
1.3 |
0.75 |
1.4 |
0.79 |
70 |
0.268 |
0.443 |
0.75 |
0.67 |
0.84 |
0.73 |
95 |
0.193 |
0.32 |
0.67 |
0.61 |
0.75 |
0.67 |
120 |
0.153 |
0.253 |
0.61 |
0.42 |
0.69 |
0.47 |
150 |
0.124 |
0.206 |
0.42 |
0.39 |
0.47 |
0.43 |
185 |
0.0991 |
0.164 |
0.38 |
0.37 |
0.42 |
0.4 |
240 |
0.0754 |
0.125 |
0.34 |
0.34 |
0.38 |
0.37 |
300 |
0.0601 |
0.1 |
0.31 |
0.31 |
0.35 |
0.34 |
400 |
0.047 |
— |
0.22 |
0.22 |
— |
— |
500 |
0.0366 |
— |
0.2 |
0.2 |
— |
— |
630 |
0.0283 |
— |
0.18 |
0.18 |
— |
— |
800 |
0.0221 |
— |
0.13 |
0.13 |
— |
— |
1 000 |
0.0176 |
— |
0.12 |
0.12 |
— |
— |
Maximum resistance of conductor and armour for two-, three-, four- and five-core cables having wire armour
1) With stranded copper conductor
Nominal cross sectional area of conductor |
Maximum resistance per km of cable at 20 °C |
Copper conductor |
Aluminum conductor |
Steel wire armour |
Cables with stranded copper conductors |
Two-core |
Three-core |
Four-core |
Five-core |
600/1000 V |
600/1000 V |
1900/3300 V |
600/1000 V |
600/1000 V |
mm2 |
Ω |
Ω |
Ω |
Ω |
Ω |
Ω |
Ω |
1.5 |
12.1 |
— |
10.2 |
9.5 |
— |
8.8 |
8.2 |
2.5 |
7.41 |
— |
8.8 |
8.2 |
— |
7.7 |
6.8 |
4 |
4.61 |
— |
7.9 |
7.5 |
— |
6.8 |
6.2 |
6 |
3.08 |
— |
7 |
6.7 |
— |
4.3 |
3.9 |
10 |
1.83 |
— |
6 |
4 |
— |
3.7 |
3.4 |
16 |
1.15 |
1.91 |
3.7 |
3.5 |
1.9 |
3.1 |
2.2 |
25 |
0.727 |
1.2 |
3.7 |
2.5 |
1.7 |
2.0 2.3 |
1.8 |
35 |
0.524 |
0.868 |
2.6 |
2.3 |
1.8 |
— |
1.6 |
50 |
0.387 |
0.641 |
2.3 |
2 |
1.3 |
1.8 |
1.1 |
70 |
0.268 |
0.443 |
2 |
1.8 |
1.2 |
1.2 |
0.94 |
95 |
0.193 |
0.32 |
1.4 |
1.3 |
1.1 |
1.1 |
— |
120 |
0.153 |
0.253 |
1.3 |
1.2 |
0.76 |
0.76 |
— |
150 |
0.124 |
0.206 |
1.2 |
0.78 |
0.71 |
0.68 |
— |
185 |
0.099 1 |
0.164 |
0.82 |
0.71 |
0.65 |
0.61 |
— |
240 |
0.075 4 |
0.125 |
0.73 |
0.63 |
0.59 |
0.54 |
— |
300 |
0.060 1 |
0.1 |
0.67 |
0.58 |
0.55 |
0.49 |
— |
400 |
0.047 0 |
— |
0.59 |
0.52 |
0.5 |
0.35 |
— |
2) With solid aluminum conductor
Nominal cross-sectional area of conductor |
Maximum resistance per km of cable at 20 °C |
Copper conductor |
Aluminum conductor |
Steel wire armour |
Cables with solid aluminum conductors |
Two-core |
Three-core |
Four-core |
600/1000 V |
600/1000 V |
1900/3300 V |
600/ 1000 V |
mm2 |
Ω |
Ω |
Ω |
Ω |
Ω |
Ω |
1.5 |
12.1 |
— |
— |
— |
— |
— |
2.5 |
7.41 |
— |
— |
— |
— |
— |
4 |
4.61 |
— |
— |
— |
— |
— |
6 |
3.08 |
— |
— |
— |
— |
— |
10 |
1.83 |
— |
— |
— |
— |
— |
16 |
1.15 |
1.91 |
4 |
3.8 |
2 |
3.4 |
25 |
0.727 |
1.2 |
4.1 |
2.7 |
1.9 |
2.4 |
35 |
0.524 |
0.868 |
2.9 |
2.5 |
1.9 |
2.2 |
50 |
0.387 |
0.641 |
2.6 |
2.2 |
1.4 |
1.9 |
70 |
0.268 |
0.443 |
2.3 |
1.9 |
1.3 |
1.3 |
95 |
0.193 |
0.32 |
1.6 |
1.4 |
1.2 |
1.2 |
120 |
0.153 |
0.253 |
— |
1.2 |
0.82 |
0.82 |
150 |
0.124 |
0.206 |
— |
0.86 |
0.76 |
0.74 |
185 |
0.099 1 |
0.164 |
— |
0.76 |
0.71 |
0.67 |
240 |
0.075 4 |
0.125 |
— |
0.68 |
0.64 |
0.59 |
300 |
0.060 1 |
0.1 |
— |
0.63 |
0.59 |
0.54 |
400 |
0.047 0 |
— |
— |
— |
— |
— |
Electrical Properties(600/1000 V)
1) Single core with copper conductor
Nominal area of conductor |
Single Core Stranded Copper Conductors |
Current Ratings |
Approximate voltage drop per ampereper metre |
Direct in ground |
In singleway ducts |
Installed in air |
Ground |
Duct |
Air |
mm² |
amps |
amps |
amps |
mV |
mV |
mV |
50 |
235 |
235 |
222 |
0.87 |
0.93 |
0.87 |
70 |
290 |
280 |
285 |
0.62 |
0.70 |
0.62 |
95 |
345 |
330 |
346 |
0.47 |
0.56 |
0.47 |
120 |
390 |
370 |
402 |
0.39 |
0.48 |
0.39 |
150 |
435 |
405 |
463 |
0.33 |
0.43 |
0.33 |
185 |
490 |
440 |
529 |
0.28 |
0.39 |
0.28 |
240 |
560 |
500 |
625 |
0.24 |
0.35 |
0.24 |
300 |
630 |
550 |
720 |
0.21 |
0.32 |
0.21 |
400 |
700 |
580 |
815 |
0.20 |
0.30 |
0.20 |
500 |
770 |
620 |
918 |
0.18 |
0.28 |
0.18 |
630 |
840 |
670 |
1027 |
0.17 |
0.26 |
0.17 |
800 |
888 |
692 |
1119 |
0.17 |
0.25 |
0.17 |
1000 |
942 |
735 |
1214 |
0.16 |
0.24 |
0.16 |
1) Single core with aluminum conductor
Nominal area of conductor |
Single Core Aluminum Conductors |
Current Ratings |
Approximate voltage drop per ampereper metre |
Direct in ground |
In singleway ducts |
Installed in air |
Ground |
Duct |
Air |
mm² |
amps |
amps |
amps |
mV |
mV |
mV |
50 |
175 |
180 |
162 |
1.40 |
1.60 |
1.40 |
70 |
220 |
220 |
207 |
0.98 |
1.00 |
0.98 |
95 |
260 |
260 |
252 |
0.72 |
0.79 |
0.74 |
120 |
295 |
295 |
292 |
0.58 |
0.66 |
0.60 |
150 |
330 |
330 |
337 |
0.48 |
0.57 |
0.49 |
185 |
375 |
365 |
391 |
0.39 |
0.49 |
0.41 |
240 |
435 |
410 |
465 |
0.31 |
0.42 |
0.34 |
300 |
490 |
455 |
540 |
0.27 |
0.38 |
0.29 |
400 |
540 |
480 |
625 |
0.35 |
0.38 |
0.25 |
500 |
580 |
510 |
714 |
0.31 |
0.35 |
0.22 |
630 |
630 |
540 |
801 |
0.28 |
0.32 |
0.20 |
2) Two cores with copper conductor
Nominal area of conductor |
Two Cores Stranded Copper Conductors |
Current Ratings |
Approximate voltage drop per ampere per metre |
Direct in ground |
In single way ducts |
Installed in air |
Ground |
Duct |
Air |
mm² |
amps |
amps |
amps |
mV |
mV |
mV |
16* |
140 |
115 |
115 |
2.9 |
2.9 |
2.9 |
25* |
180 |
145 |
152 |
1.9 |
1.9 |
1.9 |
35* |
215 |
175 |
188 |
1.3 |
1.3 |
1.3 |
50 |
255 |
210 |
228 |
1.0 |
1.0 |
1.0 |
70 |
315 |
260 |
291 |
0.7 |
0.7 |
0.7 |
2) Two cores with aluminum conductor
Nominal area of conductor |
Two Cores Aluminum Conductors |
Current Ratings |
Approximate voltage drop per ampere per metre |
Direct in ground |
In single way ducts |
Installed in air |
Ground |
Duct |
Air |
mm² |
amps |
amps |
amps |
mV |
mV |
mV |
25* |
135 |
110 |
112 |
3.1 |
3.1 |
3.1 |
35* |
165 |
130 |
138 |
2.2 |
2.2 |
2.2 |
50 |
195 |
155 |
166 |
1.7 |
1.7 |
1.7 |
70 |
240 |
195 |
211 |
1.1 |
1.1 |
1.1 |
95 |
288 |
237 |
254 |
0.8 |
0.8 |
0.8 |
3) Three cores with copper conductor
Nominal area of conductor |
Three Cores Stranded Copper Conductors |
Current Ratings |
Approximate voltage drop per ampereper metre |
Direct in ground |
In singleway ducts |
Installed in air |
Ground |
Duct |
Air |
mm² |
amps |
amps |
amps |
mV |
mV |
mV |
16 |
115 |
94 |
99 |
2.5 |
2.5 |
2.5 |
25 |
150 |
125 |
131 |
1.7 |
1.7 |
1.7 |
35 |
180 |
150 |
162 |
1.2 |
1.2 |
1.2 |
50 |
215 |
175 |
197 |
0.9 |
0.9 |
0.9 |
70 |
265 |
215 |
251 |
0.6 |
0.6 |
0.6 |
95 |
315 |
260 |
304 |
0.5 |
0.5 |
0.5 |
120 |
360 |
300 |
353 |
0.4 |
0.4 |
0.4 |
150 |
405 |
335 |
406 |
0.3 |
0.3 |
0.3 |
185 |
460 |
380 |
463 |
0.3 |
0.3 |
0.3 |
240 |
530 |
440 |
546 |
0.2 |
0.2 |
0.2 |
300 |
590 |
495 |
628 |
0.2 |
0.2 |
0.2 |
400 |
667 |
570 |
728 |
0.2 |
0.2 |
0.2 |
3) Three cores with aluminum conductor
Nominal area of conductor |
Three Cores Aluminum Conductors |
Current Ratings |
Approximate voltage drop per ampereper metre |
Direct in ground |
In singleway ducts |
Installed in air |
Ground |
Duct |
Air |
mm² |
amps |
amps |
amps |
mV |
mV |
mV |
16 |
89 |
72 |
74 |
4.2 |
4.2 |
4.2 |
25 |
115 |
94 |
98 |
2.7 |
2.7 |
2.7 |
35 |
135 |
110 |
120 |
1.9 |
1.9 |
1.9 |
50 |
165 |
135 |
145 |
1.4 |
1.4 |
1.4 |
70 |
200 |
165 |
185 |
1.0 |
1.0 |
1.0 |
95 |
240 |
200 |
224 |
0.7 |
0.7 |
0.7 |
120 |
275 |
230 |
264 |
0.6 |
0.6 |
0.6 |
150 |
310 |
255 |
305 |
0.5 |
0.5 |
0.5 |
185 |
350 |
295 |
350 |
0.4 |
0.4 |
0.4 |
240 |
410 |
340 |
418 |
0.3 |
0.3 |
0.3 |
300 |
460 |
385 |
488 |
0.3 |
0.3 |
0.3 |
400 |
520 |
443 |
562 |
0.2 |
0.2 |
0.2 |
4) Four cores with copper conductor
Nominal area of conductor |
Four Cores Stranded Copper Conductors |
Current Ratings |
Approximate voltage drop per ampereper metre |
Direct in ground |
In singleway ducts |
Installed in air |
Ground |
Duct |
Air |
mm² |
amps |
amps |
amps |
mV |
mV |
mV |
16 |
115 |
94 |
99 |
2.5 |
2.5 |
2.5 |
25 |
150 |
125 |
131 |
1.7 |
1.7 |
1.7 |
35 |
180 |
150 |
162 |
1.2 |
1.2 |
1.2 |
50 |
215 |
175 |
197 |
0.9 |
0.9 |
0.9 |
70 |
265 |
215 |
251 |
0.6 |
0.6 |
0.6 |
95 |
315 |
260 |
304 |
0.5 |
0.5 |
0.5 |
120 |
360 |
300 |
353 |
0.4 |
0.4 |
0.4 |
150 |
405 |
335 |
406 |
0.3 |
0.3 |
0.3 |
185 |
460 |
380 |
463 |
0.3 |
0.3 |
0.3 |
240 |
530 |
440 |
546 |
0.2 |
0.2 |
0.2 |
300 |
590 |
495 |
628 |
0.2 |
0.2 |
0.2 |
400 |
667 |
570 |
728 |
0.2 |
0.2 |
0.2 |
500 |
720 |
605 |
800 |
0.2 |
0.2 |
0.2 |
4) Four cores with aluminum conductor
Nominal area of conductor |
Four Cores Aluminum Conductors |
Current Ratings |
Approximate voltage drop per ampereper metre |
Direct in ground |
In singleway ducts |
Installed in air |
Ground |
Duct |
Air |
mm² |
amps |
amps |
amps |
mV |
mV |
mV |
16 |
89 |
72 |
74 |
4.2 |
4.2 |
4.2 |
25 |
115 |
94 |
98 |
2.7 |
2.7 |
2.7 |
35 |
135 |
110 |
120 |
1.9 |
1.9 |
1.9 |
50 |
165 |
135 |
145 |
1.4 |
1.4 |
1.4 |
70 |
200 |
165 |
185 |
1.0 |
1.0 |
1.0 |
95 |
240 |
200 |
224 |
0.7 |
0.7 |
0.7 |
120 |
275 |
230 |
264 |
0.6 |
0.6 |
0.6 |
150 |
310 |
255 |
305 |
0.5 |
0.5 |
0.5 |
185 |
350 |
295 |
350 |
0.4 |
0.4 |
0.4 |
240 |
410 |
340 |
418 |
0.3 |
0.3 |
0.3 |
300 |
460 |
385 |
488 |
0.3 |
0.3 |
0.3 |
400 |
520 |
443 |
562 |
0.2 |
0.2 |
0.2 |
500 |
561 |
470 |
618 |
0.2 |
0.2 |
0.2 |
Electrical Properties(1900/3300 V)
Nominal area of conductor |
Single Core Stranded CopperConductors |
Nominal area of conductor |
Three Core Stranded CopperConductors |
Current Ratings |
Current Ratings |
Direct in ground |
In single wayducts |
Installed in air |
Direct in ground |
In single wayducts |
Installed in air |
mm² |
amps |
amps |
amps |
mm² |
amps |
amps |
amps |
50 |
222 |
219 |
228 |
16 |
114 |
96 |
106 |
70 |
271 |
264 |
285 |
25 |
147 |
124 |
142 |
95 |
324 |
310 |
350 |
35 |
175 |
147 |
168 |
120 |
366 |
342 |
407 |
50 |
207 |
174 |
202 |
150 |
409 |
376 |
463 |
70 |
254 |
214 |
255 |
185 |
460 |
414 |
528 |
95 |
304 |
257 |
312 |
240 |
528 |
464 |
623 |
120 |
345 |
293 |
361 |
300 |
589 |
506 |
710 |
150 |
387 |
328 |
410 |
400 |
651 |
535 |
808 |
185 |
436 |
371 |
471 |
500 |
720 |
579 |
915 |
240 |
502 |
428 |
554 |
630 |
789 |
624 |
1030 |
300 |
563 |
480 |
634 |
800 |
831 |
650 |
1119 |
- |
- |
- |
- |
1000 |
880 |
689 |
1214 |
- |
- |
- |
- |