600/1000V XLPE Insulated, PVC Sheathed, Armoured Power Cables to IEC 60502 (Single Core)
FGD300 1RVMAV-R (CU/XLPE/PVC/AWA/PVC 600/1000V Class 2)
VDE Code: N2XRY
Application
The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings.This product type is TUV approved.
Standards
Basic design to to IEC 60502-1
Approvals
TUV Certification (Z1 17 01 98200 004)
Fire Performance
Flame Retardance (Single Vertical Wire Test) | IEC 60332-1 |
Voltage Rating
600/1000V
Cable Construction
Conductor | Annealed copper wire, stranded according to IEC 60228 class 2. |
Insulation | XLPE according to IEC 60502-1. |
Inner Covering | Extruded PVC or polymeric compound. |
Armouring | Aluminium wire |
Outer Sheath | Extruded PVC Type ST1/ST2 according to IEC 60502-1. |
Outer Sheath Option | UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request. |
Colour Code
Insulation Colour | Brown or blue, other colours can be offered upon request. |
Sheath Colour | Black, other colours can be offered upon request. |
Mechanical and Electrical Properties
Maximum temperature range during operation | 80°C (For ST1 Sheath); 90°C (For ST2 Sheath) | ||||||
Maximum short circuit temperature (5 Seconds) | 250°C | ||||||
Minimum bending radius | |||||||
|
Construction Parameters
Conductor | FGD300 1RVMAV-R | ||||||
---|---|---|---|---|---|---|---|
No. of Cores xCross Section | Class of Conductor | Nominal Insulation Thickness | Nominal Inner Covering Thickness |
Nominal Armour Wire Diameter |
Nominal Sheath Thickness | Approx. Overall Diameter |
Approx. Weight |
No.xmm2 | mm | mm | mm | mm | mm | kg/km | |
1x1.5 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 10.2 | 150 |
1x2.5 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 10.6 | 169 |
1x4.0 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 11.2 | 196 |
1x6.0 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 11.7 | 228 |
1x10 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 12.7 | 290 |
1x16 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 13.7 | 372 |
1x25 | 2 | 0.9 | 1.0 | 0.8 | 1.8 | 15.4 | 507 |
1x35 | 2 | 0.9 | 1.0 | 1.25 | 1.8 | 17.5 | 681 |
1x50 | 2 | 1.0 | 1.0 | 1.25 | 1.8 | 19.0 | 848 |
1x70 | 2 | 1.1 | 1.0 | 1.25 | 1.8 | 21.0 | 1116 |
1x95 | 2 | 1.1 | 1.0 | 1.6 | 1.8 | 24.0 | 1511 |
1x120 | 2 | 1.2 | 1.0 | 1.6 | 1.8 | 25.8 | 1821 |
1x150 | 2 | 1.4 | 1.0 | 1.6 | 1.8 | 27.8 | 2165 |
1x185 | 2 | 1.6 | 1.0 | 1.6 | 1.8 | 30.4 | 2655 |
1x240 | 2 | 1.7 | 1.0 | 1.6 | 1.9 | 33.5 | 3352 |
1x300 | 2 | 1.8 | 1.0 | 2.0 | 2.0 | 37.5 | 4224 |
1x400 | 2 | 2.0 | 1.2 | 2.0 | 2.2 | 41.3 | 5263 |
1x500 | 2 | 2.2 | 1.2 | 2.0 | 2.3 | 44.2 | 7379 |
1x630 | 2 | 2.4 | 1.2 | 2.5 | 2.4 | 49.8 | 9611 |
1x800 | 2 | 2.6 | 1.4 | 2.5 | 2.6 | 55.3 | 11896 |
1x1000 | 2 | 2.8 | 1.4 | 2.5 | 2.7 | 60.4 | 14467 |
ELECTRICAL PROPERTIES
Conductor Operating Temperature | 90°C |
Ambient Temperature | 30°C |
Current-Carrying Capacities (Amp) according to BS 7671: 2008 table 4E3A
Conductor cross-sectional area |
Reference Method C (clipped direct) |
Reference Method F (in free air or on a perforated cable tray, horizontal or vertical) | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Touching | Touching | Spaced by on cable diameter | |||||||||
2 cables, singlephase a.c. or d.c. flat |
3 or 4 cables, threephase a.c. flat |
2 cables, singlephase a.c. or d.c. flat |
3 or 4 cables, threephase a.c. flat |
3 cables threephase a.c. trefoil |
2 cables, d.c. | 2 cables, single-phase a.c. |
3 or 4 cables, three-phase a.c. |
||||
Horizontal | Vertical | Horizontal | Vertical | Horizontal | Vertical | ||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
mm2 | A | A | A | A | A | A | A | A | A | A | A |
50 | 237 | 220 | 253 | 232 | 222 | 284 | 270 | 282 | 266 | 288 | 266 |
70 | 303 | 277 | 322 | 293 | 285 | 356 | 349 | 357 | 337 | 358 | 331 |
95 | 367 | 333 | 389 | 352 | 346 | 446 | 426 | 436 | 412 | 425 | 393 |
120 | 425 | 383 | 449 | 405 | 402 | 519 | 497 | 504 | 477 | 485 | 449 |
150 | 488 | 437 | 516 | 462 | 463 | 600 | 575 | 566 | 539 | 549 | 510 |
185 | 557 | 496 | 587 | 524 | 529 | 688 | 660 | 643 | 614 | 618 | 574 |
240 | 656 | 579 | 689 | 612 | 625 | 815 | 782 | 749 | 714 | 715 | 666 |
300 | 755 | 662 | 792 | 700 | 720 | 943 | 906 | 842 | 805 | 810 | 755 |
400 | 853 | 717 | 899 | 767 | 815 | 1137 | 1094 | 929 | 889 | 848 | 797 |
500 | 962 | 791 | 1016 | 851 | 918 | 1314 | 1266 | 1032 | 989 | 923 | 871 |
630 | 1082 | 861 | 1146 | 935 | 1027 | 1528 | 1474 | 1139 | 1092 | 992 | 940 |
800 | 1170 | 904 | 1246 | 987 | 1119 | 1809 | 1744 | 1204 | 1155 | 1042 | 978 |
1000 | 1261 | 961 | 1345 | 1055 | 1214 | 2100 | 2026 | 1289 | 1238 | 1110 | 1041 |
Voltage Drop (Per Amp Per Meter) according to BS 7671: 2008 table 4E3B
Nominal Cross Section Area | 2 cables d.c. | Ref. Methods C&F(clipped direct, on trays or in free air) | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
2 cables, single-phase a.c. | 3 or 4 cables, three-phase a.c. | |||||||||||||||
Touching | Spaced* | Trefoil and touching | Flat and touching | Flat and spaced* | ||||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | ||||||||||
mm2 | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | ||||||||||
γ | γ | r | x | z | r | x | z | r | x | z | r | x | z | r | x | z |
50 | 0.98 | 0.99 | 0.21 | 1.0 | 0.98 | 0.29 | 1.0 | 0.86 | 0.18 | 0.87 | 0.64 | 0.25 | 0.88 | 0.84 | 0.33 | 0.9 |
70 | 0.67 | 0.68 | 0.20 | 0.71 | 0.69 | 0.29 | 0.75 | 0.59 | 0.170 | 0.62 | 0.60 | 0.25 | 0.65 | 0.62 | 0.32 | 0.70 |
95 | 0.49 | 0.51 | 0.195 | 0.55 | 0.53 | 0.28 | 0.60 | 0.44 | 0.170 | 0.47 | 0.46 | 0.24 | 0.52 | 0.49 | 0.31 | 0.58 |
120 | 0.39 | 0.41 | 0.190 | 0.45 | 0.43 | 0.27 | 0.51 | 0.35 | 0.165 | 0.39 | 0.38 | 0.24 | 0.44 | 0.41 | 0.30 | 0.51 |
150 | 0.31 | 0.33 | 0.185 | 0.38 | 0.36 | 0.27 | 0.45 | 0.29 | 0.160 | 0.33 | 0.31 | 0.23 | 0.39 | 0.34 | 0.29 | 0.45 |
185 | 0.25 | 0.27 | 0.185 | 0.33 | 0.30 | 0.26 | 0.40 | 0.23 | 0.160 | 0.28 | 0.26 | 0.23 | 0.34 | 0.29 | 0.29 | 0.41 |
240 | 0.195 | 0.21 | 0.180 | 0.28 | 0.24 | 0.26 | 0.35 | 0.180 | 0.155 | 0.24 | 0.21 | 0.22 | 0.30 | 0.24 | 0.28 | 0.37 |
300 | 0.155 | 0.17 | 0.175 | 0.25 | 0.195 | 0.25 | 0.32 | 0.145 | 0.150 | 0.21 | 0.170 | 0.22 | 0.28 | 0.20 | 0.27 | 0.34 |
400 | 0.115 | 0.145 | 0.170 | 0.22 | 0.180 | 0.24 | 0.30 | 0.125 | 0.150 | 0.195 | 0.160 | 0.21 | 0.27 | 0.20 | 0.27 | 0.33 |
500 | 0.093 | 0.125 | 0.170 | 0.21 | 0.165 | 0.24 | 0.29 | 0.105 | 0.145 | 0.180 | 0.145 | 0.20 | 0.25 | 0.190 | 0.24 | 0.31 |
630 | 0.073 | 0.105 | 0.165 | 0.195 | 0.150 | 0.23 | 0.27 | 0.092 | 0.145 | 0.170 | 0.135 | 0.195 | 0.24 | 0.175 | 0.23 | 0.29 |
800 | 0.056 | 0.090 | 0.160 | 0.190 | 0.145 | 0.23 | 0.27 | 0.086 | 0.140 | 0.165 | 0.130 | 0.180 | 0.23 | 0.175 | 0.195 | 0.26 |
1000 | 0.045 | 0.092 | 0.155 | 0.180 | 0.140 | 0.21 | 0.25 | 0.080 | 0.135 | 0.155 | 0.125 | 0.170 | 0.21 | 0.165 | 0.180 | 0.24 |
Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance