6.35/11kV XLPE Insulated, MDPE Sheathed, Armoured MV Power Cables (Single Core)

N2XSYB2Y (CU/XLPE/CS/PVC/ATA/PE 6.35/11kV Class 2)

N2XSYR2Y (CU/XLPE/CS/PVC/AWA/PE 6.35/11kV Class 2)

Caledonian No.: FGD300 12RVMAX-R (CU/XLPE/CS/PVC/ATA or AWA/PE 6.35/11kV Class 2)

Application

They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations.

Standards

Basic design adapted to IEC 60502-2

Construction

IEC60502 Single Core Cables

Conductor : Plain annealed copper wire, stranded according to IEC/BS EN 60228 class 2..

Conductor Screen : Extruded layer of semi-conducting cross-linkable compound is applied over the conductor and shall cover the surface completely.

Insulation : Extruded cross-linked compound type (XLPE)

Insulaton Screen : Extruded layer of semi-conducting cross-linkable compound is applied over the insulation.

Metallic Screen : The metallic layer shall be applied as a collective screen. The metallic screen shall consist of either copper tapes or a concentric layer of copper wires or a combination of tapes and wires.

Separation Sheath : Thermoplastic PVC compound.

Armour : Aluminium tape or Aluminium wire.

Outer Sheath : Thermoplastic MDPE compound Type ST7 according to IEC 60502-2.The overall cable design will be more suitable for wet locations.

Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance and anti-rodent can be offered as option.

COLOUR CODE

Insulation Colour : Natural colouring.

Sheath Colour : Red

PHYSICAL PROPERTIES

Operating Temperature : up to 90°C

Temperature Range: -5°C

Short Circuit Temperature( 5 seconds maximum duration ) : 250°C

Bending Radius : 20 x OD

Nominal /Operating /Testing Voltages

Rated Voltage Uo/U Operating Voltage (Um) Testing Voltage (rms)
6.35/11KV 12KV 25.5KV

DIMENSIONAL DATA

N2XSYB2Y (CU/XLPE/CS/PVC/ATA/PE 6.35/11kV Class 2)

Nom. Cross-Section Area Nom. Insulation Thickness Copper Wire Screen Area Copper Tape Screen Area Nom. Bedding Thickness Nom. Armour Tape Thickness Nom.Sheath Thickness Approx. Overall Diameter Approx. Weight
mm² mm mm² mm² mm mm mm mm kg/km
70 3.4 16 8.2 1.2 0.5 1.9 30.8 7590
95 3.4 16 8.9 1.2 0.5 1.9 32.4 6240
120 3.4 16 9.8 1.2 0.5 2.0 34.0 5150
150 3.4 25 10.4 1.2 0.5 2.1 36.7 4160
185 3.4 25 11.2 1.2 0.5 2.1 37.4 3260
240 3.4 25 12.4 1.2 0.5 2.2 40.1 3010
300 3.4 25 13.4 1.2 0.5 2.2 42.1 2650
400 3.4 35 14.6 1.2 0.5 2.4 46.2 2214
500 3.4 35 16.2 1.3 0.5 2.5 49.0 2020
630 3.4 35 18.9 1.4 0.5 2.6 54.4 1700

N2XSYR2Y (CU/XLPE/CS/PVC/AWA/PE 6.35/11kV Class 2)

Nom. Cross-Section Area Nom. Insulation Thickness Copper Wire Screen Area Copper Tape Screen Area Nom. Bedding Thickness Nom. Armour Wire Diameter Nom.Sheath Thickness Approx. Overall Diameter Approx. Weight
mm² mm mm² mm² mm mm mm mm kg/km
70 3.4 16 8.2 1.2 1.6 1.9 32.0 8230
95 3.4 16 8.9 1.2 1.6 1.9 33.6 6780
120 3.4 16 9.8 1.2 1.6 2.0 35.2 5589
150 3.4 25 10.4 1.2 1.6 2.1 37.9 4490
185 3.4 25 11.2 1.2 2.0 2.1 39.4 3490
240 3.4 25 12.4 1.2 2.0 2.2 42.1 3240
300 3.4 25 13.4 1.2 2.0 2.2 44.1 2870
400 3.4 35 14.6 1.2 2.0 2.4 48.2 2430
500 3.4 35 16.2 1.3 2.5 2.5 52.0 2130
630 3.4 35 18.9 1.4 2.5 2.6 57.4 1840

ELECTRICAL DATA

Nom. Cross- Section Area D C Resistance A C Resistance Short Circuit Rating of Conductor 1 sec Capacitance Charging Current Short Circuit Rating of Screen 1 sec Reactance Inductance Impedance
Copper Wire Copper Tape Trefoil Flat Spaced Trefoil Flat Spaced Trefoil Flat Spaced
mm² µΩ/m µΩ/m kA pF/m mA/m kA µΩ/m µΩ/m nH/m nH/m µΩ/m µΩ/m
70 268 343 9.8 288 0.58 1.96 1.19 122 188 390 600 364 386
95 193 248 13.3 323 0.65 1.96 1.31 122 182 390 580 272 300
120 153 196 17.2 353 0.71 1.96 1.43 116 172 370 550 225 257
150 124 159 21.2 380 0.76 3.06 1.52 110 166 350 530 193 229
185 99 128 26.6 416 0.83 3.06 1.63 107 166 340 530 165 206
240 75 98 34.9 460 0.92 3.06 1.81 104 163 330 520 140 185
300 60 80 43.8 506 1.01 3.06 1.95 100 157 320 500 126 174
400 47 64 57.3 561 1.12 4.29 2.13 94 154 300 490 113 164
500 37 51 72.3 619 1.24 4.29 2.37 91 151 290 480 105 158
630 28 42 91.2 698 1.37 4.29 2.75 91 148 290 470 97 151

CURRENT RATING FOR SINGLE CORE 3.6/6KV(UM=7.2KV ) TO 18/30KV(UM=36KV) XLPE INSULATION

Nom. Cross-Section Area Buried direct in Ground Laid in Single Way Duct Laid in Air
Trefoil Flat spaced Trefoil Flat Touching Trefoil Flat Touching Flat spaced
mm² A A A A A A A
70 239 246 227 229 296 303 356
95 285 293 271 274 361 369 434
120 323 332 308 311 417 426 500
150 361 366 343 347 473 481 559
185 406 410 387 391 543 550 637
240 469 470 447 453 641 647 745
300 526 524 504 510 735 739 846
400 590 572 564 571 845 837 938
500 650 672 604 661 935 938 1118
630 700 882 654 771 1045 1048 1318

Current Rating Conditions

Ground Temperature : 20°C

Ambient Temperature (air) : 30°C

Depth of Soil : 0.8m

Thermal Resistance of Soil : 1.5K•m/W