THHN/THWN 600V, PVC/Nylon Insulated & PVC Sheathed Power Cable |
|
Application: |
These cables are designed for use in power, control and lighting circuits in a broad range of commercial and industrial applications. Suitable for installation indoors or outdoors, aerially, in conduits, ducts, cable trays or direct burial in circuits not exceeding 600 volts. May be used in NEC Class I and II, Division 2 hazardous locations. Recognised for use in continuous rating at 75¡ãC in wet locations, 90¡ãC continuous rating in dry locations, 130¡ãC for emergency overload ratings, and 250¡ãC for short circuit ratings. |
|
Conductor: |
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8. |
|
Insulation: |
High dielectric strength flame-retardant PVC per UL 1581. |
|
Insulation Jacket: |
Clear nylon per UL 1581 for Type TIII1N or TIIWN wire. |
|
Cabling: |
Three or more conductors are assembled with fillers as needed. A Nylon rip cord is put under the jacket for ease of stripping. |
|
Grounding Conductor: |
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 sized in accordance with UL 1277. |
|
Overall Jacket: |
Sunlight-resistant gas/vaportight PVC per UL 1277. |
|
Flame Tests: |
70,000 BTU/hr Cable Tray Propagation Test per ICEA 383 |
|
Color Code: |
ICEA Method 4 |
|
Additional Standards: |
UL Type TC per Article 336 of the NEC. |
|
Three Cores |
Size
AWG
or
kcmil |
Stranding |
Ampacity |
Nominal Thickness of Insulation (mils/mm) |
Grounding Conductors Three Per Cable(awg) |
Nominal Thickness of Jacket (mils/mm) |
Nominal Overall Diameter (inches/mm) |
Approx.Weight(lbs/1000ft) |
|
|
59
79
104
136
|
30/0.76
30/0.76
40/1.01
40/1.01
|
|
60/1.52
80/2.03
80/2.03
80/2.03
|
0.63/16
0.72/18.3
0.84/21.4
0.97/24.7
|
320
420
690
980
|
1
1/0
2/0
3/0
4/0 |
|
|
50/1.27
50/1.27
50/1.27
50/1.27
50/1.27
|
|
80/2.03
80/2.03
80/2.03
80/2.03
80/2.03
|
1.11/28.2
1.20/30.5
1.29/32.8
1.40/35.6
1.52/38.6
|
|
|
|
|
|
|
110/2.78
110/2.78
110/2.78
|
1.72/43.9
1.96/49.8
2.23/56.7 |
|
|
|
Four Cores |
Size
AWG
or
kcmll |
Stranding |
Ampacity |
Nominal Grounding
Thickness
of Insulation(mils/mm) |
Grounding Conductors Three Per Cable(awg) |
Nominal Thickness of Jacket(mils/mm) |
Nominal Overall Diameter (inches/mm) |
Approx.Weight(lbs/1000ft) |
|
|
47
63
83
110 |
30/0.76
30/0.76
40/1.01
40/1.01 |
12
10
10
8 |
60/1.52
60/1.52
80/2.03
80/2.03 |
0.69/17.5
0.77/19.6
0.93/23.6
1.07/27.2 |
380
540
825
1225 |
1
1/0
2/0
3/0
|
|
|
50/1.27
50/1.27
50/1.27
50/1.27 |
8
6
8
6 |
80/2,03
80/2.03
80/2.03
80/2.03 |
1.23/31.2
1.27/33.0
1.43/36.3
1.55/39.4 |
1525
1800
2440
2630 |
|
|
230
256
315
391 |
50/1.27
60/1.52
60/1.52
60/1.52 |
6
6
6
4 |
110/2.78
110/2.78
110/2.78
110/2.78 |
1.74/44.2
1.92/48.8
2.17/55.1
2.48/63.1 |
3490
4100
5660
8150 |
|
|