FROR 300/500 V

Flexible multicore cable, flame retardant and with reduced emission of corrosive gases.


Normative references:

 

  Italian standard: CPT 007 CEI 20-22 II
  Colours code: CEI UNEL 00722/ HD 308

 

Construction:

  • 1 - Flexible copper class 5 CEI EN 60228
  • 2 - PVC TI2
  • 3 - PVC TM2

Characteristics:

  • Rated voltage: 300/500 V
  • Operating Temperature: +5°C - +60° C on the conductor
  • Max. temperature of short circuit: 160° C on the conductor (max. duration 5 seconds)
  • Min. bending radius: Mobile installation: 12 x outer diameter
      Fixed installation: 6 x outer diameter

Applications:

 

Section Max diam. conductor Insulation thickness sheath thickness Outer diameter Max cond. resist. at 20°C Cable weight
mm2 mm mm mm mm ohms/km kg/km
7 G 1 0.21 0.6 1.0 9.4 19.5 175
10 G 1 0.21 0.6 1.2 12.2 19.5 255
12 G 1 0.21 0.6 1.2 12.6 19.5 290
14 G 1 0.21 0.6 1.3 13.4 19.5 335
16 G 1 0.21 0.6 1.3 14.1 19.5 380
19 G 1 0.21 0.6 1.4 15.1 19.5 435
24 G 1 0.21 0.6 1.5 16.7 19.5 550
27 G 1 0.21 0.6 1.6 19.3 19.5 615
7 G 1.5 0.26 0.7 1.2 11.1 13.3 240
10 G 1.5 0.26 0.7 1.3 14.2 13.3 335
12 G 1.5 0.26 0.7 1.4 14.9 13.3 390
14 G 1.5 0.26 0.7 1.4 15.6 13.3 445
16 G 1.5 0.26 0.7 1.5 16.7 13.3 515
19 G 1.5 0.26 0.7 1.5 17.5 13.3 585
24 G 1.5 0.26 0.7 1.7 20.8 13.3 745
27 G 1.5 0.26 0.7 1.8 21.5 13.3 825