DeviceNet™

Applications

DeviceNet™ communication link is based on proven CAN technology.DeviceNet™ is a bus system developed by Allen Bradley (Rockwell Automation). These cables are used to interconnect various industrial devices, such as SPS controls or limit switches. The special characteristic of this bus system is that a data pair and a power supply pair are integrated in one cable.

Construction

  DeviceNetTM
Application DeviceNet Trunk (Thick) DeviceNet Drop (Thin)
Cable Construction 1x2x0.96mm² +1x2x1.53mm² 1x2x0.24mm²+1x2x0.38mm²
Inner Conductor Diameter (data pair) Copper, tinned (AWG 18/19) Copper, tinned (AWG 24/19)
Inner Conductor Diameter (power pair) Copper, tinned (AWG 15/19) Copper, tinned (AWG 22/19)
Conductor Insulation (data pair) Foam-skin-PE/PE Foam-skin-PE/PE
Conductor Insulation (power pair) PVC/ PE PVC/ PE
Conductor Colors 1 light blue, white light blue, white
Conductor Colors 2 red, black red, black
Stranding Element Double conductor Double conductor
Shielding Polyester foil, aluminum-lined Polyester foil, aluminum-lined
Drain Wire yes yes
Total Shielding Copper braid, tinned Copper braid, tinned
Outer Jacket Material PVC/ PUR/ PE/ FRNC PVC/ PUR/ PE/ FRNC
Outer Cable Diameter 12.0 mm ± 0.3 mm 7.0 mm ± 0.3 mm
Outer Jacket Color Grey/ Violet/ Yellow Grey/ Violet/ Yellow
For armored cable
Inner Jacket Material PVC/ PUR/ PE/ FRNC PVC/ PUR/ PE/ FRNC
Armor SWA / SWB SWA / SWB
Outer Jacket Material PVC/ PUR/ PE/ FRNC PVC/ PUR/ PE/ FRNC
Outer Cable Diameter Min. 16.0 mm Min. 10.5mm
Outer Jacket Color Grey/ Violet/ Yellow Grey/ Violet/ Yellow

Fire resistant DeviceNet™ cables can also be provided upon request.

Electrical Data

Characteristic Impedance@1MHz 120 Ω ± 10Ω 120 Ω ± 10Ω
Conductor Resistance 22.6 Ohm/km max. 90.0 Ohm/km max.
Insulation Resistance 0.20 GOhm x km min. 0.20 GOhm x km min.
Mutual Capacitance@800MHz 39.8 nF/km nom. 39.8 nF/km nom.
Working Voltage Max: 300V Max: 300V
Test Voltage 2.0 KV 2.0 KV
Data Rate 125 Kbit/s 500m 125 Kbit/s 100m
250 Kbit/s 250m 250 Kbit/s 100m
500 Kbit/s 100m 500 Kbit/s 100m
Attenuation 125 KHz < 0.42 dB/100m 125 KHz < 0.95 dB/100m
500 KHz < 0.81 dB/100m 500 KHz < 1.64 dB/100m
1 MHz < 1.26 dB/100m 1 MHz < 2.38 dB/100m

Technical Data

Weight (Approx.) 195.0 kg/km 69.0 kg/km
Min. Bending Radius (Laying) 10 x OD mm 10 x OD mm
Operating Temp.Range (Min.) - 20 °C - 20 °C
Operating Temp.Range (Max.) +80 °C +80 °C